Plan Review Notes
Plan Review Notes For Permit 04080987
Permit Number 04080987
Review Stop B
Sequence Number 6
Notes
Date Text
2004-12-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISED PLANS SUBMITTED 12/7/04.
  
 1) FBC 1006.2.4PROTECTION OF EXTERIOR
 EXIT STAIR.SEE SHEET LS-1 FOR REDLINED
 COMMENT.AMEND THE PLAN TO INCORPORATE
 THE NOTE BEFORE RESUBMITTAL.
  
 2) FBC* 11-4.3.2(1)ACCESSIBLE ROUTE
 TO BUILDING ENTRANCE.SHEET A1-1, THE
 ACCESSIBLE CAR PARKING AND
 ACCESSIBILITY
 RAMPS HAVE BEEN REVISED, AMEND THE
 PLANS
 TO SHOW THE ACCESSIBLE ROUTE FROM
 PARKING TO THE ENTRY LOBBY (MAIN
 ENTRANCE).
  
 3) FBC* F102.2.8SHEETS A1-2, A2-1,
 A4-3 AND A4-4 ALL REFER TO A FABRIC
 AWNING OVER THE ENTRANCE.PERMANENT
 CANOPIES/ AWNINGS AND THEIR SUPPORTS,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE OF NON-COMBUSTIBLE
 MATERIAL, FIRE RETARDANT TREATED WOOD,
 WOOD OF TYPE III SIZES OR OF 1-HOUR
 RESISTANT CONSTRUCTION.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 4) FBC 1608.2.2THE GUARDRAIL STRENGTH
 NOTE HAS BEEN REMOVED FROM SHEETS A4-3
 AND A4-4.THERE ARE STILL TWO
 GUARDRAILS SHOWN ON SECTION 01/A5-1 AND
 WEST ELEVATION 01/A4-4 (ALSO SHOWN ON
 SECOND FLOOR PLAN - SHEET A1-2).THE
 GUARDRAILS SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB APPLIED IN ANY DIRECTION AT THE
 TOP OF THE GUARDRAIL, A CONCENTRATED
 HORIZONTAL LOAD OF 200 LB APPLIED ON A
 1
 SQ FT AREA AT ANY POINT, AND A LINE
 LOAD OF 50 PLF APPLIED HORIZONTALLY AT
 THE REQUIRED GUARDRAIL HEIGHT WITH A
 SIMULTANEOUS LINE LOAD OF 100 PLF
 APPLIED VERTICALLY DOWNWARD ON THE TOP
 OF THE GUARDRAIL. THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY (UNLESS NOTED
 ABOVE) BUT SHALL BE APPLIED
 INDIVIDUALLY
 TO PRODUCE MAXIMUM STRESS IN EACH OF
 THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE DESIGN LOADS.
 ALSO, THE ELEVATOR 'BRIDGE' GUARDRAIL
 HEIGHT REQUIREMENT OF 42" SHALL BE
 ANNOTATED ON THE PLANS.
  
 5) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
  
  
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]