Plan Review Notes
Plan Review Notes For Permit 04080987
Permit Number 04080987
Review Stop E
Sequence Number 2
Notes
Date Text
2004-10-06 00:00:00********PROVISO/REVISION *************
  
 1)NOTE: PLEASE SEE ELEVATOR DISCONNECT
 IS STILL SHOWN AS 100A W/ A 150A FEED.
 THIS DISCONNECT MUST BE RATED AT 150A'S
 AND MAY HAVE THE 100A FUSES AS NOTED.
 THIS HAS BEEN REDLINED ON PLANS.
 PLEASE REVISE BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  