2004-10-06 00:00:00 | ********PROVISO/REVISION ************* | | | | 1)NOTE: PLEASE SEE ELEVATOR DISCONNECT | | IS STILL SHOWN AS 100A W/ A 150A FEED. | | THIS DISCONNECT MUST BE RATED AT 150A'S | | AND MAY HAVE THE 100A FUSES AS NOTED. | | THIS HAS BEEN REDLINED ON PLANS. | | PLEASE REVISE BEFORE ROUGH ELECTRICAL | | INSPECTION. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|