2004-08-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR |
| TOILET ROOMS SHOWING COMPLIANCE WITH |
| SECTIONS 11-4.16, 11-4.19, & 11-4.22 & |
| ALL SUBSECTIONS. SHOW MEASUREMENTS TO |
| THE CENTER OF THE W/C OFF THE WALL AND |
| THE CENTER OF LAV OFF WALL. SEE FIG 28 |
| FOR THE W/C AND LAV MIN. 15" TO CENTER |
| ON CLEAR FLOOR SPACE. |
| 2) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR |
| DRINKING FOUNTAINS SHOWING COMPLIANCE |
| WITH SECTION 11-4.15. |
| 3) COMMENT ADDRESSED ON PERMIT 04081108 |
| 4) COMMENT ADDRESSED ON PERMIT 04081108 |
| 5) SHT A2-2 DETAILS 04 & 08 SHOW HEIGHT |
| AND WIDTH FOR SCUPPERS AND OVERFLOW |
| SCUPPERS. SECTION 104.2.1 |
| 6) SHT PO.1 GENERAL SPECIFICATIONS #24, |
| AIR CHAMBERS ARE NOT APPROVED. DELETE |
| REFERENCE. SECTION 604.9 |
| 7) IN THE REMOVAL OF ANY PARY OF A |
| DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO- |
| HIBITED. SECTION 704.5 - ALL CAPPED PIP- |
| ES SHALL BE CAPPED WITH A PERMINATE CAP |
| 8) SHT P2.2 WATER RISER DIAGRAM, AIR |
| CHAMBERS ARE NOT APPROVED. DELETE FROM |
| THE RISER DIAGRAM. IS WATER HAMMER ARR- |
| ESTORS ARE INSTALLED THEY SHALL BE LOCA- |
| TED NEAR THE FIXTURE IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING. PDI-WH 201. |
| 9) SHT P3.1 TANKLESS WATER HEATERS SHALL |
| BE LISTED. SUBMIT MANUF. SPECIFICATIONS |
| SECTION 303.4 |
| |