Plan Review Notes
Plan Review Notes For Permit 04080987
Permit Number 04080987
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 &
 ALL SUBSECTIONS. SHOW MEASUREMENTS TO
 THE CENTER OF THE W/C OFF THE WALL AND
 THE CENTER OF LAV OFF WALL. SEE FIG 28
 FOR THE W/C AND LAV MIN. 15" TO CENTER
 ON CLEAR FLOOR SPACE.
 2) SHTS A1-1 & A1-2 SUBMIT A DETAIL FOR
 DRINKING FOUNTAINS SHOWING COMPLIANCE
 WITH SECTION 11-4.15.
 3) COMMENT ADDRESSED ON PERMIT 04081108
 4) COMMENT ADDRESSED ON PERMIT 04081108
 5) SHT A2-2 DETAILS 04 & 08 SHOW HEIGHT
 AND WIDTH FOR SCUPPERS AND OVERFLOW
 SCUPPERS. SECTION 104.2.1
 6) SHT PO.1 GENERAL SPECIFICATIONS #24,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 604.9
 7) IN THE REMOVAL OF ANY PARY OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PRO-
 HIBITED. SECTION 704.5 - ALL CAPPED PIP-
 ES SHALL BE CAPPED WITH A PERMINATE CAP
 8) SHT P2.2 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 THE RISER DIAGRAM. IS WATER HAMMER ARR-
 ESTORS ARE INSTALLED THEY SHALL BE LOCA-
 TED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING. PDI-WH 201.
 9) SHT P3.1 TANKLESS WATER HEATERS SHALL
 BE LISTED. SUBMIT MANUF. SPECIFICATIONS
 SECTION 303.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]