Plan Review Notes For Permit 04080987 |
Permit Number |
04080987 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-09-01 00:00:00 | **********DENIED************************ | | | | 1) EXTERIOR STAIRS ALL OPENINGS WITHIN | | 10 FEET SHALL BE 1 HOUR FIRE RATED. ON | | SHEET LS-1 SHOWS OPENINGS WITHIN 10 FEET | | TO THE RIGHT APPEARS NOT TO BE 1 HOUR | | FIRE RATED. | | | | 2) INTERIOR WALL AND CEILING FINISH | | SHALL COMPLY WITH CH. 38.3.3.2. | | | | 3) BUILDING ADDRESS IS REQUIRED. | | | | 4) SEPARATE PLANS AND PERMIT APPLICATION | | ARE REQUIRED FOR THE FIRE ALARM SYSTEM. | | | | NATE MCCRAY, CAPTAIN | | 835-2910 OR 805-6722 |
|