Notes
Date Text
2004-09-01 00:00:00**********DENIED************************
  
 1) EXTERIOR STAIRS ALL OPENINGS WITHIN
 10 FEET SHALL BE 1 HOUR FIRE RATED. ON
 SHEET LS-1 SHOWS OPENINGS WITHIN 10 FEET
 TO THE RIGHT APPEARS NOT TO BE 1 HOUR
 FIRE RATED.
  
 2) INTERIOR WALL AND CEILING FINISH
 SHALL COMPLY WITH CH. 38.3.3.2.
  
 3) BUILDING ADDRESS IS REQUIRED.
  
 4) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR THE FIRE ALARM SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 835-2910 OR 805-6722