2004-09-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1006.2.4SHEET LS-1,PROTECTION
 OF EXTERIOR EXIT STAIRS.THE ONE-HOUR
 FIRE RATED WALL SHOWN ON THE FIRST AND
 SECOND FLOOR LIFE SAFETY PLANS SHALL BE
 EXTENDED TO COVER AN AREA THAT EXTENDS
 10 FEET BEYOND THE EDGE OF THE LANDING.
 ALTERNATIVEY, THE PAINTED METAL WALL
 PANEL ASSEMBLY (SHEET A1-2, KEY NOTE 10)
 SHALL BE FIRE-RATED.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 2) FBC 1015.4SHEET A4-4.THE 'TYPICAL
 NOTE' COVERING STRENGTH OF GUARDRAILS
 SHALL ALSO APPLY TO THE METAL WALL PANEL
 (KEY NOTE ITEM 9).AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 3) FBC 2405.2THE GLAZED PANELS
 ADJACENT DOORS 101 AND 110 ARE IN A
 'HAZARDOUS LOCATION' AND ARE REQUIRED TO
 BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 4) FBC* F102.2.7SHEET A4-3, FOAM
 MOULDING (KEY NOTE 21).ARCHITECTURAL
 TRIM ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 5) SUBMIT A PRODUCT APPROVAL FOR THE
 MODIFIED BITUMEN ROOFING SYSTEM
 REFERENCED ON SHEET A2-1, ROOF PLAN.
 ALSO, (FBC* F102.2.4) ROOF COVERINGS ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE NEW
 WINDOWS AND GLASS BLOCK AND FOR EXTERIOR
 DOORS 101, 105, 106 AND 207.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 7) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 8) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS