2004-09-15 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) FBC 1006.2.4SHEET LS-1,PROTECTION |
| OF EXTERIOR EXIT STAIRS.THE ONE-HOUR |
| FIRE RATED WALL SHOWN ON THE FIRST AND |
| SECOND FLOOR LIFE SAFETY PLANS SHALL BE |
| EXTENDED TO COVER AN AREA THAT EXTENDS |
| 10 FEET BEYOND THE EDGE OF THE LANDING. |
| ALTERNATIVEY, THE PAINTED METAL WALL |
| PANEL ASSEMBLY (SHEET A1-2, KEY NOTE 10) |
| SHALL BE FIRE-RATED.AMEND THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 2) FBC 1015.4SHEET A4-4.THE 'TYPICAL |
| NOTE' COVERING STRENGTH OF GUARDRAILS |
| SHALL ALSO APPLY TO THE METAL WALL PANEL |
| (KEY NOTE ITEM 9).AMEND THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 3) FBC 2405.2THE GLAZED PANELS |
| ADJACENT DOORS 101 AND 110 ARE IN A |
| 'HAZARDOUS LOCATION' AND ARE REQUIRED TO |
| BE SAFETY GLASS SATISFYING THE |
| REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201).SUBMIT DETAILS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 4) FBC* F102.2.7SHEET A4-3, FOAM |
| MOULDING (KEY NOTE 21).ARCHITECTURAL |
| TRIM ON BUILDINGS LOCATED IN THE FIRE |
| DISTRICT, SHALL BE CONSTRUCTED OF |
| APPROVED NON-COMBUSTIBLE MATERIALS OR |
| FIRE RETARDANT TREATED WOOD.ANNOTATE |
| THE PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 5) SUBMIT A PRODUCT APPROVAL FOR THE |
| MODIFIED BITUMEN ROOFING SYSTEM |
| REFERENCED ON SHEET A2-1, ROOF PLAN. |
| ALSO, (FBC* F102.2.4) ROOF COVERINGS ON |
| BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| SHALL CONFORM TO THE REQUIREMENTS OF |
| CLASS A OR B ROOF COVERINGS, AS DEFINED |
| IN FBC 1505.ANNOTATE THE PLANS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 6) SUBMIT PRODUCT APPROVALS FOR THE NEW |
| WINDOWS AND GLASS BLOCK AND FOR EXTERIOR |
| DOORS 101, 105, 106 AND 207. |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE |
| WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| |
| 7) PRODUCT APPROVAL.RULE 9B-72 FAC. |
| FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE |
| PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL |
| CAN BE ACHIEVED IF THERE IS A QUALITY |
| ASSURANCE PROGRAM IN PLACE WITH A STATE |
| APPROVED QUALITY ASSURANCE ENTITY.IF |
| NEITHER IS APPLICABLE, THEN SITE |
| SPECIFIC APPROVAL IS REQUIRED.LOCAL |
| PRODUCT APPROVAL WILL ALLOW A PRODUCT TO |
| BE USED, IN ACCORDANCE WITH THE TEST |
| CRITERIA, THROUGHOUT THE JURISDICTION OF |
| WEST PALM BEACH.SITE SPECIFIC PRODUCT |
| APPROVAL WILL ALLOW A PRODUCT TO BE |
| USED ONLY ON THE PROJECT FOR WHICH THAT |
| SITE SPECIFIC APPROVAL IS GRANTED. |
| LOCAL AND SITE SPECIFIC PRODUCT APPROVAL |
| APPLICATION FORMS ARE AVAILABLE FROM |
| THIS OFFICE.APPROVED QUALITY ASSURANCE |
| ENTITIES ARE LISTED ON THE DCA WEBSITE: |
| WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_ |
| REGI_SRCH.ASP |
| |
| 8) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |