2004-11-01 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING |
| POOLS |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, |
| OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW. |
| 1) FBC-2001424.2.6.6.2 SHOW |
| COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE |
| MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO |
| NOTES) |
| 2) INDICATE MAXIMUM LENGTH TO VENT LINE |
| CONNECTION. |
| 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO |
| SUCTION INLETS SHALL BE PROVIDED FOR EA |
| PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| OR LOCATED ON TWO DIFFERENT PLANES. |
| (DETAIL)-THE PIPING SCHEMATIC SHOWS NO |
| MINIMUM MEASURMENT. PLEASE INDICATE THE |
| MINIMUM MEASURMENT ON PLANS. SECTION |
| 104.2.1. |
| 4) FBC-2001 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) |
| 5) FBC-2001 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 6) FBC02001 424.2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE |
| PLANS |
| AND PERMIT REQUIRED. |
| 7) VACUUM LINE NOT SHOWN ON POOL LAYOUT |
| SHEET. THIS IS SHOWN ON THE PIPING |
| DIAGRAM. PLEASE CLARIFY AND CORRELATE |
| PLANS. SECTION 104.2.1 |
| 8) NOTE STATES HEATER IS EXCEMPT FROM |
| STATE ENERGY CODE. GAS HEATERS ARE NOT |
| 90% EFFECIENT. DELETE NOTE. SECTION |
| 104.2.1 |
| 9) PIPING SCHEMATIC SHOWS A 109K HEAT |
| PUMP, BUT POOL EQUIPMENT INDICATES A |
| 400K NATURAL GAS POOL HEATER. PLEASE |
| CLARIFY, AND CORRELATE PLANS. SECTION |
| 104.2.1 |