Plan Review Notes
Plan Review Notes For Permit 04080974
Permit Number 04080974
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING
 POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS,
 OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) FBC-2001424.2.6.6.2 SHOW
 COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE
 MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO
 NOTES)
 2) INDICATE MAXIMUM LENGTH TO VENT LINE
 CONNECTION.
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)-THE PIPING SCHEMATIC SHOWS NO
 MINIMUM MEASURMENT. PLEASE INDICATE THE
 MINIMUM MEASURMENT ON PLANS. SECTION
 104.2.1.
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 6) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE
 PLANS
 AND PERMIT REQUIRED.
 7) VACUUM LINE NOT SHOWN ON POOL LAYOUT
 SHEET. THIS IS SHOWN ON THE PIPING
 DIAGRAM. PLEASE CLARIFY AND CORRELATE
 PLANS. SECTION 104.2.1
 8) NOTE STATES HEATER IS EXCEMPT FROM
 STATE ENERGY CODE. GAS HEATERS ARE NOT
 90% EFFECIENT. DELETE NOTE. SECTION
 104.2.1
 9) PIPING SCHEMATIC SHOWS A 109K HEAT
 PUMP, BUT POOL EQUIPMENT INDICATES A
 400K NATURAL GAS POOL HEATER. PLEASE
 CLARIFY, AND CORRELATE PLANS. SECTION
 104.2.1
 10)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]