2006-09-20 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE PLANS STILL SHOW AN |
| INDIVIDUA METER ALONG WITH TWO MAINS |
| WHICH IS HOW THE ORIGINAL RISER WAS |
| SHOWN. IF THIS EQUIPMENT IS A METER/MAIN |
| COMBO PANEL, THEN PLANS SHOW THIS ON |
| PLANS ON THE SIDE OF THE DWELLING. |
| 106.1.2 FBC. |
| |
| 2) NOTE: PLEASE SEE LOAD CALCULATIONS |
| AND PLEASE SEE NEC 220.31. |
| PLEASE SEE A/C LOADS MAY NOT BE DE-RATED |
| IN WITH GEN LTS AND RECEPTS. A/C LOAD IS |
| CURRENLTY BEING DE-RATED AT 65% AND THEN |
| AGAIN AT 40%. |
| PLEASE KNOW, BASED ON THE LOADS ON |
| PANELS, THE LOAD FOR THE SERVICE IS |
| SUBSTANTIALLY HIGHER THAN THE LOAD |
| SHOWN. |
| |
| 3) NOTE: PLEASE SEE MISSIGN RECEPT IN |
| BEDRM #4. |
| MORE THAN 2' OF WALL REQUIRES A RECEPT. |
| 210.52 |
| |
| 4) NOTE: PLEASE SEE 210.8A7, PLEASE SEE |
| ANY RECEPT WITHIN 6FT OF THE SINK'S EDGE |
| IN THE LAUNDRY RM IS REQUIRED TO BE GFI |
| / GFI PROTECTED. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |