2006-08-11 00:00:00 | ********* UNSAT ********* |
| |
| ** PLEASE SEE SOME ITEMS ARE THE SAME AS |
| COMMENTS WHICH WERE REDLINED ON PLANS IN |
| "NOV 04". |
| PLEASE ALSO SEE NEW COMMENTS AS PLANS |
| HAVE BEEN REVISED. |
| |
| 1) NOTE: PLEASE SEE MIN GEC PER 250.66/ |
| 310.15B6AS 1/0. THIS SIZE WAS REDLINED |
| ON ORIGINAL PLANS. |
| |
| 2) NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM THE MAINS TO |
| THE SUBPANELS. |
| 250.110.,250.24B,250.122 ETC. |
| |
| 3) NOTE: PLEASE CORRELATE PLANS WITH |
| RISER. PLEASE SEE RISER NOW SHOWS WHAT |
| APPEARS TO BE A METER/MAIN COMBO, YET |
| NOT CLEAR AS NO MAIN IS SHOWN?? |
| PLEASE SEE 230.70, PLEASE SEE PLANS |
| STILL SHOWS TWO MAIN DISCONNECTS AS ON |
| ORIG RISER. PLEASE SEE PLANS ARE NOT |
| CLEAR FOR THE SCENARIO . WHERE IS THE |
| OCP FOR PANEL "B", IS THERE FEED-THRU |
| LUGS? ETC ETC. |
| |
| 4) NOTE: PLEASE SEE LOAD CALCULATIONS |
| ARE NOT COMPLETE FOR ALL EQUIPMENT AND |
| FOR SERVICE. PLEASE SEE NEC 220.31 ETC |
| AS LOADS ARE NOT COMPLETED, A/C LOADS |
| ARE NOT SHOWN IN CALCS WHICH MAY NOT BE |
| DERATED WITH THE GEN LT/RECEPTS. |
| PLEASE SEE LOADS FOR PANEL "B" ARE NOT |
| SHOWN IN WITH THE OTHER. ETC. |
| 408.4,310.16,240.4 230.70. |
| |
| 5) NOTE: PLEASE SEE MISSING REDLINED |
| RECEPTS ON PLANS PER 210.52 |
| |
| 6) NOTE: PLEASE SEE MISSING POOL PANEL |
| ON PLANS WHICH IS SHOWN ON RISER. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 7) NOTE: PLEASE SEE DISCONNECT |
| CLEARENCES PER 110.26 FOR ALL |
| DISCONNECTS. PLEASE SEE A/C EQUIPMENT |
| SIDE OF HOUSE. |
| |
| 8) NOTE: PLEASE SEE PLANS NOW INCLUDE |
| ALL NEW LV SKR WIRINGAND SPKRS WHICH |
| WERE NOT ON ORIGINAL PLANS OR PERMIT. |
| PLEASE SUBMIT THIE UNDER A SEPARATE |
| PERMIT APPLICATION, PLANS AND FEES FOR |
| COMPLETE SCOPE OF WORK. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |