2006-08-11 00:00:00********* UNSAT *********
  
 ** PLEASE SEE SOME ITEMS ARE THE SAME AS
 COMMENTS WHICH WERE REDLINED ON PLANS IN
 "NOV 04".
 PLEASE ALSO SEE NEW COMMENTS AS PLANS
 HAVE BEEN REVISED.
  
 1) NOTE: PLEASE SEE MIN GEC PER 250.66/
 310.15B6AS 1/0. THIS SIZE WAS REDLINED
 ON ORIGINAL PLANS.
  
 2) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM THE MAINS TO
 THE SUBPANELS.
 250.110.,250.24B,250.122 ETC.
  
 3) NOTE: PLEASE CORRELATE PLANS WITH
 RISER. PLEASE SEE RISER NOW SHOWS WHAT
 APPEARS TO BE A METER/MAIN COMBO, YET
 NOT CLEAR AS NO MAIN IS SHOWN??
 PLEASE SEE 230.70, PLEASE SEE PLANS
 STILL SHOWS TWO MAIN DISCONNECTS AS ON
 ORIG RISER. PLEASE SEE PLANS ARE NOT
 CLEAR FOR THE SCENARIO . WHERE IS THE
 OCP FOR PANEL "B", IS THERE FEED-THRU
 LUGS? ETC ETC.
  
 4) NOTE: PLEASE SEE LOAD CALCULATIONS
 ARE NOT COMPLETE FOR ALL EQUIPMENT AND
 FOR SERVICE. PLEASE SEE NEC 220.31 ETC
 AS LOADS ARE NOT COMPLETED, A/C LOADS
 ARE NOT SHOWN IN CALCS WHICH MAY NOT BE
 DERATED WITH THE GEN LT/RECEPTS.
 PLEASE SEE LOADS FOR PANEL "B" ARE NOT
 SHOWN IN WITH THE OTHER. ETC.
 408.4,310.16,240.4 230.70.
  
 5) NOTE: PLEASE SEE MISSING REDLINED
 RECEPTS ON PLANS PER 210.52
  
 6) NOTE: PLEASE SEE MISSING POOL PANEL
 ON PLANS WHICH IS SHOWN ON RISER.
 FBC 106.1.2 ADMIN SECT.
  
 7) NOTE: PLEASE SEE DISCONNECT
 CLEARENCES PER 110.26 FOR ALL
 DISCONNECTS. PLEASE SEE A/C EQUIPMENT
 SIDE OF HOUSE.
  
 8) NOTE: PLEASE SEE PLANS NOW INCLUDE
 ALL NEW LV SKR WIRINGAND SPKRS WHICH
 WERE NOT ON ORIGINAL PLANS OR PERMIT.
 PLEASE SUBMIT THIE UNDER A SEPARATE
 PERMIT APPLICATION, PLANS AND FEES FOR
 COMPLETE SCOPE OF WORK.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved