Plan Review Notes For Permit 04080887
Permit Number 04080887
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-29 00:00:00******** NOTES REDLINED *********
  
 PLEASE SEE SOME ITEMS ON FIRTS REVIEW.
  
 1)NOTE: PLEASE SEE GEC IS SHOWN AS #1,
 WHEN 250.66 REQUIRES 1/0, REDLINED.
  
 2)NOTE: PLEASE SEE A GEC/EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN FROM
 METER TO FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 THIS IS NOT
 PERMITTED TO BE INSTALLED.
  
 3)NOTE: REDLINED SD'S TO BE ADDED INSIDE
 AND OUTSIDE "STUDY"THIS IS CONSIDERED TO
 BE AN ADAPTABLE SLEEPING ROOM WITH THE
 ADDED CLOSET.
  
 4)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52
  
  
 **** PLEASE SEE PLANS HAVE BEEN REDLINED
 WITH MOST OF THE ABOVE AND NEED TO BE
 REVISED WHEN ANY OTHER REVISIONS ARE
 SUBMITTED BEFORE ROUGH. ****