Plan Review Notes For Permit 04080887 |
Permit Number |
04080887 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-29 00:00:00 | ******** NOTES REDLINED ********* | | | | PLEASE SEE SOME ITEMS ON FIRTS REVIEW. | | | | 1)NOTE: PLEASE SEE GEC IS SHOWN AS #1, | | WHEN 250.66 REQUIRES 1/0, REDLINED. | | | | 2)NOTE: PLEASE SEE A GEC/EQUIPMENT | | GROUNDING CONDUCTOR IS BEING SHOWN FROM | | METER TO FIRST MEANS OF DISCONNECT. | | PLEASE SEE 250.6, 250.24 THIS IS NOT | | PERMITTED TO BE INSTALLED. | | | | 3)NOTE: REDLINED SD'S TO BE ADDED INSIDE | | AND OUTSIDE "STUDY"THIS IS CONSIDERED TO | | BE AN ADAPTABLE SLEEPING ROOM WITH THE | | ADDED CLOSET. | | | | 4)NOTE: PLEASE SEE SOME RECEPTS MISSING | | PER 210.52 | | | | | | **** PLEASE SEE PLANS HAVE BEEN REDLINED | | WITH MOST OF THE ABOVE AND NEED TO BE | | REVISED WHEN ANY OTHER REVISIONS ARE | | SUBMITTED BEFORE ROUGH. **** |
|