2004-08-28 00:00:00 | DENIED: | | 1.PLEASE PROVIDE ENERGY AND MANUAL J | | CALCULATIONS IN ACCORDANCE WITH 2002 FBC | | CHATPER 13 SUB-CHAPTER 6. | | | | 2. AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 3.A MINIMUM OF 4" AROUND THE AHU IS | | REQUIRED PER 2001 FBC(M) 603.1.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|