2004-08-28 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2002 FBC
 CHATPER 13 SUB-CHAPTER 6.
  
 2. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 3.A MINIMUM OF 4" AROUND THE AHU IS
 REQUIRED PER 2001 FBC(M) 603.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.