Date |
Text |
2004-08-25 00:00:00 | ************* UNSAT ***************** |
| |
| 1)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| * PLEASE EITHER ADD A SD IN WHAT APPEARS |
| TO BE MASTER BEDRM OR MOVE ONE SHOWN |
| IN HALLWAY INTO MASTER SLEEPING AREA. |
| *PLEASE SEE MISSING SD ON FIRST FLR |
| LEADING TO FLR ABOVE. |
| |
| 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION |
| ON ELECTRICAL PLANS. |
| |
| 3)NOTE: PLEASE SEE 210.52D FOR MISSING |
| GFI ON FIRST FLR BATH. |
| |
| 4)NOTE: PLEASE SEE 210.52C3 FOR KITCHEN |
| PENINSULAR. A RECEPT IS SHOWN BUT W/ |
| OVERHANG OF KITCHEN COUNTERTOP THIS |
| MAY NOT BE ABLE TO SERVE COUNTERSPACE. |
| PLEASE ALSO SEE WALL SPACE AT SAME |
| LOCATION PER 210.52 |
| |
| 5)NOTE: PLEASE SEE 210.52 FOR A FEW |
| RECEPTS MISSING. 2' OF WALL SPACE ETC. |
| |
| 6) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| **ISLAND** |
| |
| 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 210.12B 2002 NEC.PLEASE SEE CIRCUITING |
| |
| 8)NOTE: PLEASE SEE RISER SHOWS AN |
| EQUIPMENT FROM GUTTER TO MAINS/FIRST |
| MEANS OF DISC. PLEASE SEE 250.24,250.6 |
| AN EG IS NOT INSTALLED UNITL AFTER THE |
| FIRST MEANS OF DISC. |
| |
| 9)NOTE: PLEASE SEE LOCATION OF SERVICE |
| SHOWN ON PLANS. RISER SHOWS METER/GUTTER |
| AND TWO MAIN DISC'S WHICH DO NOT APPEAR |
| TO BE ABLE TO FIT IN LOCATION SHOWN. |
| PLEASE SEE 110.26 |
| |
| 10)NOTE: PLEASE CLARIFY LOCATION ON |
| SECOND FLR WHICH APPEARS TO HAVE BATH |
| RM SHOWN WITH NO ELECTRICAL? ARE THESE |
| RMS BEING BUILT AT THIS TIME? |
| LTS ETC. 210.582,210.70 |
| |
| 11)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| PLEASE SEE LOAD CALCULATIONS ARE NOT |
| SHOWN PER 220.31 . IT HAS BEEN NOTED |
| THAT LIGNING IS BEING SHOWN AS A CONNECT |
| -ED LOAD. PLEASE VERIFY WATTAGE OF |
| FIXTURES AND PLEASE SEE FBC FOR REQUIRED |
| "AIR-LOCK" TYPE FIXTURES. NOTE: MOST |
| OF THESE TYPE OF FIXTURES ARE A MAX OF |
| 75W. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |