Plan Review Notes
Plan Review Notes For Permit 04080887
Permit Number 04080887
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00************* UNSAT *****************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 * PLEASE EITHER ADD A SD IN WHAT APPEARS
 TO BE MASTER BEDRM OR MOVE ONE SHOWN
 IN HALLWAY INTO MASTER SLEEPING AREA.
 *PLEASE SEE MISSING SD ON FIRST FLR
 LEADING TO FLR ABOVE.
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ELECTRICAL PLANS.
  
 3)NOTE: PLEASE SEE 210.52D FOR MISSING
 GFI ON FIRST FLR BATH.
  
 4)NOTE: PLEASE SEE 210.52C3 FOR KITCHEN
 PENINSULAR. A RECEPT IS SHOWN BUT W/
 OVERHANG OF KITCHEN COUNTERTOP THIS
 MAY NOT BE ABLE TO SERVE COUNTERSPACE.
 PLEASE ALSO SEE WALL SPACE AT SAME
 LOCATION PER 210.52
  
 5)NOTE: PLEASE SEE 210.52 FOR A FEW
 RECEPTS MISSING. 2' OF WALL SPACE ETC.
  
 6) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 **ISLAND**
  
 7 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12B 2002 NEC.PLEASE SEE CIRCUITING
  
 8)NOTE: PLEASE SEE RISER SHOWS AN
 EQUIPMENT FROM GUTTER TO MAINS/FIRST
 MEANS OF DISC. PLEASE SEE 250.24,250.6
 AN EG IS NOT INSTALLED UNITL AFTER THE
 FIRST MEANS OF DISC.
  
 9)NOTE: PLEASE SEE LOCATION OF SERVICE
 SHOWN ON PLANS. RISER SHOWS METER/GUTTER
 AND TWO MAIN DISC'S WHICH DO NOT APPEAR
 TO BE ABLE TO FIT IN LOCATION SHOWN.
 PLEASE SEE 110.26
  
 10)NOTE: PLEASE CLARIFY LOCATION ON
 SECOND FLR WHICH APPEARS TO HAVE BATH
 RM SHOWN WITH NO ELECTRICAL? ARE THESE
 RMS BEING BUILT AT THIS TIME?
 LTS ETC. 210.582,210.70
  
 11)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE SEE LOAD CALCULATIONS ARE NOT
 SHOWN PER 220.31 . IT HAS BEEN NOTED
 THAT LIGNING IS BEING SHOWN AS A CONNECT
 -ED LOAD. PLEASE VERIFY WATTAGE OF
 FIXTURES AND PLEASE SEE FBC FOR REQUIRED
 "AIR-LOCK" TYPE FIXTURES. NOTE: MOST
 OF THESE TYPE OF FIXTURES ARE A MAX OF
 75W.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved