2005-07-21 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 PANEL "B".
 PLEASE SEE GROUPING OF MAINS PER 230.72
 PLEASE SHOW 215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL "B" TO
 PANEL "C".
 215.5,250.110,.250.24,250.122
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATE 2-OVENS ON PANEL "A", HOWEVER
 PANEL "A" DOES NOT SHOW THIS??
 PLEASE CLARIFY AND CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  