Plan Review Notes
Plan Review Notes For Permit 04080816
Permit Number 04080816
Review Stop B
Sequence Number 3
Notes
Date Text
2005-02-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PLANS FOR THE STRUCTURE APPEAR
 TO CONFLICT WITH THE EXISTING BUILDING.
 TYPE VI IS DECLARED (DWG
 #XP-N-00-02-FL).THE ADDITION IS TO BE
 OF THE SAME BUILDING TYPE AS THE
 EXISTING.
  
 2.)IS THIS BUILDING SPRINKLED?NOTE
 ON THE PLAN.SPRINKLERS REQUIRED AT
 NEW
 AREAS FOR ADDITIONS TO SPRINKLED
 BUILDINGS.PLEASE NOTE EXISTING
 BUILDING CONDITION ON THE PLAN.
  
 5.)THE PLAN FOR THE ROOFTOP STRUCTURE
 ALSO DECLARE A BUSINESS OCCUPANCY, THEN
 STATES THAT IT "SHALL NOT BE LOCATED
 WHERE ACCESSIBILITY IS REQUIRED".
 BUSINESS OCCUPANCY REQUIRES
 ACCESSIBILITY.THE PLAN PREPARED BY
 MORRISON HERSCHFIELD INDICATE THAT THIS
 IS UNINHABITABLE.IF THIS STRUCTURE
 HAS
 A BUSINESS OCCUPANCY AS DECLARED, SHOW
 COMPLIANCE WITH FBC CHAPTER 11.
  
 6.)SHOW OCCUPANCY SEPARATION
 COMPLIANCE (BETWEEN THE EXISTING
 STRUCTURE AND NEW), FBC CHAPTER 7.
  
 6.)THE PLAN FOR THE ROOFTOP STRUCTURE
 DECLARES HVHZ; CITY OF WEST PALM BEACH
 IS NOT IN THE HVHZ.
  
 7.)A TITLE BLOCK IS REQUIRED FOR THE
 ENGINEER (PLANS FOR ROOFTOP STRUCTURE).
 IF PRECISION QUINCY CORP IS THE TITLE
 BLOCK FOR THE ENGINEER, A CERTIFICATE
 OF AUTHORIZATION NUMBER IS TO BE ON THE
 PLAN.THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON THE PLAN.
 FAC61G15-23.002.
  
 8.)THE TWO SETS OF PLANS PREPARED BY
 MORRISON HERSCHFIELD ARE NOT THE SAME.
 ONE IS DATED 8/27, REVISION 2.THE
 OTHER HAS AN UNDATED SEAL, REVISION 4.
 PLEASE DATE FAC61G1-15, AND SUBMIT TWO
 IDENTICAL SETS.
  
 9.)A-S3, PROVIDE THE PRESCRIPTIVE
 STRENGTH FOR THE GUARDRAIL COMPLIANT
 WITH FBC1608.2.2(1) THROUGH (4).
  
 10.) I AM STILL UNABLE TO FIND THE ROOF
 DESIGN PRESSURE ON THE PLAN.SEE THE
 PREVIOUS LISTS, SPECIFICALLY ITEM #2 ON
 PREVIOUS LIST.DPS CANNOT BE SPECIFIED
 BY THE ROOFER.
  
 11.)SEE THE PREVIOUS LIST, ITEM #7.
 PROVIDE CALCULATIONS FOR THE EXISTING
 ROOF STRUCTURE AND ITS ABILITY TO
 ACCOMODATE THE NEW EQUIPMENT.THE
 CALCULATIONS REFER TO COLUMN CHECK,
 SHEAR WALL CHECK, FOUNDATION CHECK.
 WHAT ABOUT THE ROOF DECK?
  
 12.)PROVIDE A DATE FOR THE SEAL FOR
 THE CALCS AND THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON THE CALCS.
 SECOND TIME FOR THIS COMMENT; PLEASE
 COMPLY.THIS IS A REQUIREMENT FOR ALL
 DOCUMENTS.
  
 13.)FS553.80(2)(B), 4X FEE WILL BE
 CHARGED, SEE ATTACHED.