2004-11-05 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)AS PER DISCUSSION WITH DOR, |
| PRODUCT |
| APPROVALS FOR THE ROOF CAN BE SUBMITTED |
| AT A FUTURE DATE WHEN THE PRODUCT TO BE |
| USED IS DETERMINED.HOWEVER, THE |
| DESIGN |
| PRESSURES CANNOT BE SPECIFIED BY THE |
| ROOFER, SEE FBC1606.1.1, |
| FBC104.3.1.1(8).ALSO PROVIDE DESIGN |
| PRESSURE FOR COMPONENTS AND CLADDING |
| FOR |
| THE SHELTER. |
| |
| 3.)SEE THE PREVIOUS LIST #6; A |
| RESPONSE WAS PREPARED THAT ITEM #6 WAS |
| ADDRESSED BUT I WAS UNABLE TO FIND IT |
| ON |
| THE PLAN (IN REGARDS TO DESIGN CRITERIA |
| FOR THE RAILING). |
| |
| 4.)IT IS NOT CLEAR AS TO WHETHER ITEM |
| #5 FROM THE PREVIOUS LIST WAS |
| ADDRESSED. |
| PLEASE PROVIDE A DETAIL FOR THE |
| ANTENNAS |
| TO BE INSTALLED AT THE STAIRWELL. |
| |
| 5.)THE STRUCTURALS FOR THE SHELTER |
| SHOW STEEL FRAMING ONLY.DOES THIS |
| STRUCTURE HAVE WALLS, ROOF, ROOF |
| COVERING, AND DOORS OR WINDOWS?THE |
| ELEVATIONS ON THE ARCHITECTURALS APPEAR |
| TO HAVE ALL OF THESE ITEMS; IN CONFLICT |
| WITH THE STRUCTURALS. |
| |
| 6.)IF DOORS, WINDOWS, ROOF ARE BEING |
| INSTALLED, SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS; TEST OR EVALUATION REPORTS |
| (SUCH AS DADE COUNTY NOAS) AND FLORIDA |
| STATE PRODUCT APPROVALS.SEE FAC9B-72; |
| WWW.FLORIDABUILDING.ORG. |
| |
| 7.)PLEASE HAVE BRENDAN LARKIN, PE |
| CALL |
| ME IN REGARDS TO THE STRUCTURAL CALCS. |
| IT IS UNCLEAR AS TO WHERE THE CALCS ARE |
| FOR THE EXISTING ROOF STRUCTURE AND ITS |
| ABILITY TO ACCOMODATE THE NEW |
| EQUIPMENT, |
| INCLUDING A FACTOR OF SAFETY.CALLED |
| 11/05/04, LEFT MESSAGE 954-577-4655. |
| |
| 8.)PLEASE PROVIDE DATES FOR THE SEALS, |
| FAC61G15-23.002, FACG1-16.003,004. |
| |
| |
| ***NOTE - CALLED ANN HOCTOR AND |
| REQUESTED THAT DOR CONTACT ME TO GET |
| CLARIFICATION.11/05/04*** |
| |