Plan Review Notes For Permit 04080816 |
Permit Number |
04080816 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-09-21 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2.)THE CA NUMBER FOR MORRISON | | HERSCHFELD IS REQUIRED ON THE CALCS | | FAC61G15-23.002. | | | | 3.)THE CALCS REFER TO THE IBC AS THE | | BUILDING CODE. | | | | 4.)PROVIDE DESIGN PRESSURE REQUIREMENT | | FOR THE ROOF.SUBMIT PRODUCT APPROVAL | | FOR THE MEMBRANE (TEST REPORT AND | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | FAC9B72, WWW.FLORIDABUILDING.ORG). | | | | 5.)PENETRATIONS THROUGH THE STAIR | | ENCLOSURE ARE PROHIBITED BY FBC1006.1.3. | | 1. | | | | 6.)RAILING TO COMPLY WITH FBC1608.1.2. | | 1.SPECIFY; DO NOT QUOTE CODE REFERENCE | | NUMBER ONLY. |
|