Plan Review Notes For Permit 04080798 |
Permit Number |
04080798 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-25 00:00:00 | | | 1} PLEASE SHOW RECEPTACLE SPACING AS A | | CONTINUATION OF THE DINING ROOM PER | | 210.52(A)(1). ALSO NOTE THAT THE | | CONDUCTORS MUST BE # 12 PROTECTED BY A | | 20 AMP OCP PER 210.52(B)(1). | | | | 2} EGRESS LIGHTING IS REQUIRED PER | | 210.70(B)(1). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|