Plan Review Notes
Plan Review Notes For Permit 04080798
Permit Number 04080798
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00 
 1} PLEASE SHOW RECEPTACLE SPACING AS A
 CONTINUATION OF THE DINING ROOM PER
 210.52(A)(1). ALSO NOTE THAT THE
 CONDUCTORS MUST BE # 12 PROTECTED BY A
 20 AMP OCP PER 210.52(B)(1).
  
 2} EGRESS LIGHTING IS REQUIRED PER
 210.70(B)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  