Plan Review Notes
Plan Review Notes For Permit 04080798
Permit Number 04080798
Review Stop B
Sequence Number 1
Notes
Date Text
2004-08-24 00:00:00CHECKLIST:
 1-BRING DWGS TO PALM BEACH COUNTY TO
 CHECK IF IMPACT FEES ARE DUE OR NOT.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 2-NEED TO RECORD NOTICE OF COMMENCEMENT.
 3-PROVIDE ENERGY CALCULATIONS. SEE
 ATTACHED. COMPLETE ALL INFORMATION AND
 PREPARER AND OWNER TO SIGN AND DATE
 BOTTOM OF FORM.
 4-DRAWINGS TO SHOW ALL INFORMATION AS
 REQUIRED BY SECTION 1606.1.7 FBC 2001.
 5-DRAWINGS NEED TO SHOW ELECTRICAL WORK.
 SEE COMMENTS BY ELECTRICAL REVIEWER.
 6-CLARIFY WHAT IS A "HOMESTEAD" AS
 SHOWN ON PLANS. IF IT IS A UTILITY
 SHED, THEN PROVIDE COMPLETE PACKAGE
 SHOWING ENGINEERING FOR 140MPH WIND
 LOAD ZONE.
 **ALSO, SHOW DIMENSIONS & EXACT LOCATION
 FOR ZONING REVIEW. SEE ZONING COMMENTS
 7-DECLARED VALUE IS TOO LOW. OWES $37.20
 FOR UPDATED VALUATION.
 8-PROVIDE COMPLETE WALL SECTION THRU
 NEW CONCRETE BLOCK WALL SHOWING 1.5"
 WATER STOP AS REQ'D BY SEC. 2111.1.9
 CITY AMENDMENTS TO FBC 2001.
 **ALSO, SPECIFY INSULATION REQUIRED AT
 WALLS AND CEILING AS REQUIRED BY THE
 ENERGY CALCULATIONS.
 9-CLARIFY NOTE SPECIFYING DOWELS INTO
 EXISTING COLUMN. WHY VERTICAL #5 BARS?
 SPECIFY DOWEL SIZE, EMBEDMENTAND
 SPACING.SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 10-IDENTIFY ROOM WHERE EXISTING WINDOW
 WILL REMAIN. NEED TO VERIFY EGRESS
 REQUIREMENTS FOR BEDROOM AREAS.
 SEC. 1005.4.4 FBC 2001.
 11-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOOR AND STORM SHUTTERS AS REQ'D
 BY RULE CHAPTER 9B-72 AS OF OCTOBER
 1ST 2003.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.