Plan Review Notes For Permit 04080780 |
Permit Number |
04080780 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-01-05 00:00:00 | BUILDINIG PLAN REVIEW: FAILED | | | | 1. THE OWNER/AGENT STILL HAS NOT SIGNED | | THE ENERGY FORM. | | | | 2.THE DADE COUNTY PRODUCT APPROVAL FOR | | THE ARCH WINDOWS FOR THE BUTT GLASS | | ASSEMBLY NEEDS TO BE SUBMITTED. THE | | GLASS IS NOT IMPACT AND WILL REQUIRE | | STORM PANEL PROTECTION. ACCORDING TO | | THE | | ENGINEER THE ARCH 4500 SERIES WINDOWS | | ARE TO BE USED IN THIS ASSEMBLY. | | | | 3. THE APPLICATION FOR THE SITE | | SPECIFIC | | PRODUCT APPROVAL IS INCOMPLETE FOR THE | | BUTT GLASS WINDOWS.THE ENGINEER CANNOT | | BE THE TECHNICAL REPRESENTATIVE (6) AND | | (7) APPROVED THIRD PARTY QUALITY | | ASSURANCE ENTITY LISTED WITH THE STATE. | | THIS IS A CONFLICT OF INTEREST. THE | | DADE | | COUNTY PRODUCT APPROVAL FOR THE ARCH | | 4500 SERIES SHOULD BE SUBMITTED WITH | | THE | | SITE SPECIFIC APPLICATION. | | | | 4. THERE IS STILL A BALANCE OF $753.65 | | IN PERMIT FEES DUE. | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 805-6713 |
|