2004-08-25 00:00:00PROVISO:
 PER THE REVISED 2001 FBC(M) 601.4
 AND EXCEPTION #3; BALANCED AIR REQUIRED
 ALL INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR PROPER SIZING OF THE RETURN
 AIR.RETURN AIR SHOULD BE A MINIMUM OF
 14".
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 CONDENSATE SHALL TERMIANTE A MINIMUM OF
 12" FROM THE BUILDING STRUCTURE.2001
 FBC 1503.4.4.
  