2004-08-25 00:00:00 | PROVISO: | | PER THE REVISED 2001 FBC(M) 601.4 | | AND EXCEPTION #3; BALANCED AIR REQUIRED | | ALL INTO THE MASTER SUITE IS TO BE | | INCLUDED FOR PROPER SIZING OF THE RETURN | | AIR.RETURN AIR SHOULD BE A MINIMUM OF | | 14". | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | CONDENSATE SHALL TERMIANTE A MINIMUM OF | | 12" FROM THE BUILDING STRUCTURE.2001 | | FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|