2004-08-23 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE SEE LAUNDRY LOAD SHOWN AT
 1.2KW. PLEASE SEE 220.16 FOR MIN 1.5KW
  
 4 )NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
 PLEASE SEE 250.66 FOR SIZING OF GROUND-
 -ING ELECTRODE CONDUCTOR.
 310.15B6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  