Plan Review Notes For Permit 04080776
Permit Number 04080776
Review Stop E
Sequence Number 7
Notes
Date Text
2006-04-04 00:00:00REV'S FOR BT OUT OF OFFICE.
  
 REDLINED SD LOCATION IN MASTER BEDRM TO
 BE WITHIN 12" OF THE HIGHEST POINT ON A
 FLAT CEILING. NFPA-72 11.8..3.5
  
 METER/ PANELS ARE BACK TO BACK, VIF.
  
  
 CIRCUIT FOR UTIL/HALL LTS, SHOWS 15A OCP
 ON #12, WHICH IS OK.
 PLANS REDLINED,
  
  
 EITHER FOYER OR LIVING ROOM RQUIRES A LT
 FIXTURE OF SOME SORT FOR REQUIRED MEANS
 OF EGRESS LIGHTING. 230.70, LS 101 7.8.