Plan Review Notes For Permit 04080776 |
Permit Number |
04080776 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-25 00:00:00 | DENIED: | | 1.PLEASE PROVIDE MANUAL J CALCULATIONS | | ARE REQUIRED ALONG WITH THE ENERGY CALCS | | PER 2001 FBC CHAPTER 13 SUB-CHAPER 600 | | & 607.1.ABC.1. | | | | 2.PER THE REVISED 2001 FBC(M) 601.4 | | EXCEPTION #3, ALL AIR INTO THE MASTER | | SUITE IS TO BE INCLUDED FOR PROPER | | SIZING OF THE RETURN AIR, (I.E. BATHROOM | | CLOSET, ETC).RETURN AIR FROM THE | | MASTER SUITE IS NOT SIZED PROPERLY FOR | | BALANCED AIR RETURN. | | | | 3.PLAN DOES NOT INDICATE AIR MAKE UP | | FOR THE GAS DRYER.PLEASE PROVIDE | | CALCULATIONS FOR COMBUSTION AIR. | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 5.CONDENSATE DRAIN TO TERMINATE A | | MINIMUM OF 12" FROM THE BUILDING | | STRUCTURE PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|