Plan Review Notes
Plan Review Notes For Permit 04080776
Permit Number 04080776
Review Stop M
Sequence Number 1
Notes
Date Text
2004-08-25 00:00:00DENIED:
 1.PLEASE PROVIDE MANUAL J CALCULATIONS
 ARE REQUIRED ALONG WITH THE ENERGY CALCS
 PER 2001 FBC CHAPTER 13 SUB-CHAPER 600
 & 607.1.ABC.1.
  
 2.PER THE REVISED 2001 FBC(M) 601.4
 EXCEPTION #3, ALL AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR PROPER
 SIZING OF THE RETURN AIR, (I.E. BATHROOM
 CLOSET, ETC).RETURN AIR FROM THE
 MASTER SUITE IS NOT SIZED PROPERLY FOR
 BALANCED AIR RETURN.
  
 3.PLAN DOES NOT INDICATE AIR MAKE UP
 FOR THE GAS DRYER.PLEASE PROVIDE
 CALCULATIONS FOR COMBUSTION AIR.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 5.CONDENSATE DRAIN TO TERMINATE A
 MINIMUM OF 12" FROM THE BUILDING
 STRUCTURE PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.