2004-08-23 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | MUST COMPLY WITH 250.66, #2 MIN. | | | | 2} THE FEEDERS FROM THE DISCONNECTS TO | | THE PANELS MUST HAVE AN EQUIPMENT | | GROUND SIZED PER 250.122. | | | | 3} THE LAUNDRY CIRCIUIT MUST BE | | CALCULATED AT 1500 VA PER220.16(B). | | | | 4} PANEL "B" HAS # 14 CONDUCTORS WITH A | | 20AMP OCP. SEE 310.16. | | | | 5} THE BATH CIRCUIT MUST COMPLY WITH | | 210.11(C)(3), 20 AMP #12. | | | | 6} BEDROOM #2 RECEPTACLE SPACING MUST | | COMPLY WITH 210.52(A)(1) SPACING. | | | | 7} THERE IS ONLY ONE DISCONNECT SHOWN AT | | THE METER LOCATION BUT 2 ON THE RISER. | | PLEASE CORRELATE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|