 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250.66, #2 MIN.
  
 2} THE FEEDERS FROM THE DISCONNECTS TO
 THE PANELS MUST HAVE AN EQUIPMENT
 GROUND SIZED PER 250.122.
  
 3} THE LAUNDRY CIRCIUIT MUST BE
 CALCULATED AT 1500 VA PER220.16(B).
  
 4} PANEL "B" HAS # 14 CONDUCTORS WITH A
 20AMP OCP. SEE 310.16.
  
 5} THE BATH CIRCUIT MUST COMPLY WITH
 210.11(C)(3), 20 AMP #12.
  
 6} BEDROOM #2 RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A)(1) SPACING.
  
 7} THERE IS ONLY ONE DISCONNECT SHOWN AT
 THE METER LOCATION BUT 2 ON THE RISER.
 PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  