Date |
Text |
2004-10-21 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| COMMENTS FROM THE PREVIOUS REVIEW HAVE |
| NOT BEEN ADDRESSED, OR HAVE NOT BEEN |
| ADDRESSED PROPERLY. NUMBER OF PREVIOUS |
| REVIEW COMMENTS WILL REMAIN THE SAME TO |
| AVOID CONFUSION. |
| 1) THERE IS MORE WORK SHOWN ON THE PLAN |
| THAN IS SHOWN ON THE APPLICATION. PLEASE |
| CALRIFY. SECTION 104.2.1 |
| 4) SHOW THE FOLLOWING INFORMATION ON THE |
| ACCESSIBLE TOILET DETAIL. 11-4.16.3 |
| CLEAR FLOOR SPACE, 11-4.19.3 CLEAR FLOOR |
| SPACE. |
| 5) A WATER RISER DIAGRAM IS REQUIRED PER |
| SECTION 104.3.1.1. - THE SANITARY RISER |
| DIAGRAM SUBMITTED DOES NOT REFLECT THE |
| FLOOR PLAN. RISER SHOWS TWO W/C'S AND |
| TWO LAV'S, BUT FLOOR PLAN SHOWS ONE W/C |
| AND ONE LAV. PLEASE SHOW SECOND TOILET |
| ROOM CAPPED OFF. SECTION 104.2.1 |
| |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |