Date Text
2004-10-06 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE.
 RISER SHOWS A NEW 125A MCB PANEL YET
 PANEL SCHEDULE SUBMITTED IS 150A MCB
 PANEL?
 IS THE PANEL SCHEDULE SUBMITTED FOR THIS
 BUILT OUT AREA?
  
 2)NOTE: PLEASE VERIFY OCP FROM EXISTING
 150A SHOWN FEEDING 125A PANEL??
  
 3)NOTE: PLEASE SEE 210.62,220.12 FOR
 REQUIRED SHOW WINDOW RECEPTS.
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  