Plan Review Notes For Permit 04080738 |
Permit Number |
04080738 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-10-06 00:00:00 | ********** UNSAT *********** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | WITH PANEL SCHEDULE. | | RISER SHOWS A NEW 125A MCB PANEL YET | | PANEL SCHEDULE SUBMITTED IS 150A MCB | | PANEL? | | IS THE PANEL SCHEDULE SUBMITTED FOR THIS | | BUILT OUT AREA? | | | | 2)NOTE: PLEASE VERIFY OCP FROM EXISTING | | 150A SHOWN FEEDING 125A PANEL?? | | | | 3)NOTE: PLEASE SEE 210.62,220.12 FOR | | REQUIRED SHOW WINDOW RECEPTS. | | | | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | PLEASE SHOW PER | | 220.3,220.10,220.11,220.13 ETC. | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | AT 125% PER 215.3,230.42 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|