Plan Review Notes
Plan Review Notes For Permit 04080738
Permit Number 04080738
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
 FLORIDA ADMINISTRATIVE CODE
  
 1) THERE IS MORE WORK SHOWN ON THE PLAN
 THAN IS SHOWN ON APPLICATION. PLEASE
 CLARIFY. SECTION 104.2.1
 2) INDEX OF DRAWINGS SHOWS SHEETS A-1, &
 E-1, BUT THE ONLY SHEET SUBMITTED IS A-2
 PLEASE CLARIFY. SECTION 104.2.1
 3) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1
 4) SHOW THE FOLLOWING INFORMATION ON THE
 ACCESSIBLE TOILET DETAIL. SECTION 11-4.
 16.2 CLEAR FLOOR SPACE, SECTION 11-4.16.
 5 FLUSH CONTROLS, 11-4.19.3 CLEAR FLOOR
 SPACE, & 11-4.19.4 EXPOSED PIPES AND
 SURFACES.
 5) SHT A-2 ACCESSIBLE TOILET DETAIL
 SHOWS 18" MINIMUM CENTER TO CENTER OF
 BETWEEN THE W/C AND LAV. MINIMUM OF 30"
 IS REQUIRED PER SECTION 405.3.1
 6) A SANITARY AND WATER RISER DIAGRAM
 ARE REQUIRED PER SECTION 104.3.1.1
 7) PER SECTION 704.5 NO DEAD ENDS ALLOW-
 ED WHEN REMOVING PIPING FROM THE SANIT-
 ARY SYSTEM. ABANDONED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
 8)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)/FS 471.025
 INITIALS ARE NOT ACCEPTABLE.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - FULL SIGNATURE REQUIRED.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]