Plan Review Notes
Plan Review Notes For Permit 04080730
Permit Number 04080730
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-05 00:00:00THE COMMENTS FROM THE LAST REVIEW WHERE
 NOT ANSWERED.PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR REVIEW.
  
 1} THE FEEDER AND OVERCURRENT PROTECTION
 FOR THE "SUB-PANEL" NOW SHOWN AS BEING
 FED WITH "3/0 OCP"?
  
 2} PROVIDE A SCHEDULE FOR THE
 "SUB-PANEL" AS REQUESTED IN THE FIRST
 REVIEW.
  
 3} THE MAIN SERVICE ON THE SCHEMATIC IS
 SHOWN AS A 200 AMP, THE LOAD CALCULATION
 SUPPLIED INDICATES A 250 AMP PANEL.
 PLEASE CLARIFY.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026