 THE DRAWING NOTES INDICATE NO HEATER,
 AND NONE IS SHOWN ON THE SCHEMATIC, BUT
 A SUBMITTAL ATTACHED AND THE LOAD CALCS
 INDICATE THERE IS A HEAT PUMP, PLEASE
 CORRELATE.
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND
 CONDUIT SIZE AND TYPE, PANEL RATING AND
 OCP.
  