Plan Review Notes
Plan Review Notes For Permit 04080662
Permit Number 04080662
Review Stop E
Sequence Number 3
Notes
Date Text
2004-11-23 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE ELECTRICAL WIRING
 DIAGRAM. PLEASE SEE 50A DISC FOR 2HP
 PUMP, AND 30A DISC FOR 1HP BLOWER
 MOTOR.
 THE OCP INDICATED SEEMS TO WAY OVERSIZED
 FOR EQUIPMENT.
 240.4,430, ETC
 SINCLAIR ENG COMMENTS.
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ALL NEW LOADS ADDED TO EXISTING
 PANEL.
 THIS SHOULD BE ON A SEPARATE SHEET WITH
 BEING ON REVISED PLANS FOR HOUSE. THE
 LOAD CALCULATIONS WILL BE PART OF THIS
 PERMIT SUBMITTED FOR RECORD WITH THIS
 SET OF PLANS.
 PLEASE BE SURE PERSON RESPONSIBLE FOR
 PLANS PRINTED NAME AND SIGNS PLANS.
 FBC 104.2.1
 PLEASE SEE FS 481.223 FOR ARCH/DESIGNERS
 AND WORDS TO THAT AFFECT.
 OTHER PLANS COMMENTS.
  
 A RE-SUB FEE WILL NOT BE CHARGED FOR
 ELECTRICAL COMMENTS.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]