Plan Review Notes
Plan Review Notes For Permit 04080598
Permit Number 04080598
Review Stop E
Sequence Number 2
Notes
Date Text
2004-10-15 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE NOTES #'1 AND 2 FROM
 PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE AIC RATING IS REQ-
 -UIRED AT THIS TIME.
 110.9
  
 3)NOTE: PLEASE SEE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS STILL MISSING FROM
 MAIN TO PANEL. 250.24, 250.110. 250.122
 PLEASE ALSO SEE SIZING OF CONDUIT MAY
 BE AFFECTED ONCE EQPGRND IS ADDED.
 DEPENDING ON CONDUIT TYPE.
  
 PLEASE SEE 553.80(2)(B) THIS COPY OF FS
 IS ATTACHED AND GIVEN AS A NOTICE ONLY.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]