Plan Review Notes For Permit 04080598 |
Permit Number |
04080598 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-25 00:00:00 | DENIED: | | 1.PLAN SHEET A3 OF 4 INDICATES A 3" | | FLEX DRYER VENT.DRYER VENT SHALL BE A | | MINIMUM OF 4" & MUST HAVE A SMOOTH | | INTERIOR FINISH THEREFORE CANNOT BE FLEX | | DUCT.TERMINATION OF EXHAUST SHALL BE | | NON-SCREENED WITH A BACKDRAFT DAMPER. | | | | 2.RETURN AIR JUMPER FROM BEDROOM #2 | | SHALL BE A MINIMUM OF 10".MASTER | | BEDROOM R/A JUMPER SHALL BE A MINIMUM | | OF 14".REVISED 2001 FBC(M) 601.4 | | EXCEPTION #1 & 3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|