2004-12-10 00:00:00 | DENIED |
| |
| |
| 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 2.ORIGONAL PERMIT APPLICATION |
| MISSING. |
| SUBMIT APPLICATION WHEN RESUBMITTING |
| PLANS. |
| |
| 3.ORIGONAL PLANS MISSING, INCLUDE ONE |
| COPY OF OLD PAGES WHEN SUBMITTING NEW |
| PAGES. |
| |
| 4.NO PRODUCT APPROVALS SUBMITTED. |
| SUBMIT 2 COPIES OF PRODUCT APPROVALS |
| FOR |
| EXTERIOR DOORS, WINDOWS, BOTH ROOFING |
| PRODUCTS, IMPACT PROTECTION, STRAPS AND |
| TIE-DOWNS AND OVERHEAD DOOR. |
| ALL PRODUCT APPROVALS REQUIRE THE |
| FOLLOWING TO BE ATTACHED. |
| |
| |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 5.SUBMIT ROOF NAILING SCHEDULE SHOWING |
| SIZE OF SHEATHING, FASTENERS AND SPACING |
| OF FASTENERS. |
| |
| 6.SHOW THICKNESS AND FASTENING FOR |
| WALL SHEATHING. |
| |
| 7.SHOW TRUSS PLANS WITH UPLIFTS AND |
| STRAPS USED. INCLUDE ROOF HEIGHT AND |
| SLOPE. |
| |
| 8.SUBMIT A STRAP AND FASTENER SHCEDULE |
| SHOWING UPLIFTS AND FASTENING USED. |
| |
| 9.SHOW ATTIC ACCESS SIZE AND LOCATION |
| COMPLYING WITH FBC 2309.6 |
| |
| 10.SHOW SOFFIT DETAIL INBCLUDING |
| METHOD OF ROOF VENTILATION. |
| |
| |
| 11.1015.2 HEIGHT. GUARDRAILS SHALL |
| FORM A VERTICAL PROTECTIVE BARRIER NOT |
| LESS THAN 42" HIGH. |
| 1015.3 OPENINGS. OPEN GUARDRAILS |
| SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| REJECT THE PASSAGE OF 2" DIAMETER |
| SPHERE. |
| SHOW DETAIL ON PLANS. |
| |
| SUBMIT WINDOW SCHEDULE SHOWING LOCATION |
| OF BEDROOM WINDOW AND SILL HEIGHT SO |
| THAT WE CAN CHECK FOR EMERGENCY ESCAPE |
| RESCUE OPENING SIZES. FBC 1005.4.4 |
| |
| 12.SUBMIT ENERGY CALCS. |
| |
| 13.HISTORIC REVIEW REQIRED. |
| |
| 14. SEE ATTACED NOTICE FOR INFORMATION |
| ABOUT FL STATUTE 553.80(2)(B) |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |