Plan Review Notes For Permit 04080503 |
Permit Number |
04080503 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-11-09 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT A-1 SANITARY RISER DIAGRAM DOES | | NOT MEET CODE REQUIREMENTS. | | A) WASH MACHINE AND KITCHEN SINK SHALL | | NOT DRAIN THROUGH THE HORIZONTAL WET | | VENT OF THE BATHROOM FIXTURES. 909.1 | | (SUGGESTION: HAVE PLUMBING CONTRACTOR | | DRAW A RISER DIAGRAM THAT MEETS CODE AND | | HAVE ARCHITECT COPY AND SIGN AND SEAL | | THE RISER THAT MEETS CODE) - AN EXAMPLE | | OF A RISER THAT MEETS CODE WAS SUBMITTED | | WITH THE LAST REVIEW COMMENTS, BUT WAS | | NOT USED AS AN EXAMPLE. | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|