Plan Review Notes For Permit 04080503 |
Permit Number |
04080503 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT A-1 SANITARY RISER DIAGRAM DOES | | NOT MEET THE CODE REQUIREMENTS. | | A) WASH MACHINE AND KITCHEN SINK SHALL | | NOT DRAIN THROUGH THE WET VENTED HORI- | | ZONTAL PIPING OF THE BATHROOM FIXTURES. | | SECTION 909.1 | | B) A TRAP IS REQUIRED FOR THE SHOWER. | | SECTION 1002.1 | | C) CLEANOUT REQUIRED AT WASH MACHINE | | 4' ABOVE THE FLOOR. SECTION 708.10 | | D) DISHWASHER LINE NOT TRAPPED. D/W | | SHALL CONNEC UPSTREAM OF THE KITCHEN | | SINK OR GARBAGE DISPOSAL TRAP. | | 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | A SANT. RISER DIAGRAM THAT MEETS THE | | CODE REQUIREMENTS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|