2004-08-25 00:00:00DENIED:
 1.PLAN SHEET E-1 AIR CONDITIONING
 NOTE #16, 2ND FLOOR BEDROOM 2, 3 AND THE
 STUDY SHALL HAVE 1 1/2" DOOR UNDER CUT
 OR 1 SQUARE FOOT LOUVER FOR R/A.SEE
 THE ATTACHED REQUIREMENTS FOR RETURN AIR
 PER THE REVISED 2001 FBC(M) 601.4 SEE
 EXCEPTIONS 1 THROUGH 3.
  
 2.SECOND FLOOR PLAN INDICATES O.A.
 INTAKE FROM THE ROOF.PER 2001 FBC
 CHAPTER 13 SUB-SECTION 609.1.ABC.1 #2,
 MAKE-UP AIR SHALL NOT BE TAKEN FROM THE
 ROOFTOP.
  
 3.DUCTS SHALL NOT BE LOCATED IN OR
 WITHIN 6" OF THE GROUND PER 2001 FBC(M)
 603.12
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  