 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE #6 EQUIPMENT GROUND FROM THE
 METER TO THE PANEL MUST BE REMOVED PER
 250.6 AS IT ALLOWS A PARALLEL PATH TO
 GROUND.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER110.9.
  
 3} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 4} IF THERE IS NO DISCONNECT AT THE
 METER PLEASE SEE 230.70 CWPB
 AMMENDMENTS FOR REQUIREMENT REGARDING
 UNPROTECTED CONDUCTORS INSIDE THE
 BUILDING.
  
 5} A SERVICE RECEPTACLE MUST BE ADDED
 FOR THE A/C PER 210.63.
  
 6} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING PER
 210.52(E).
  
 7} SMOKE DETECTORS ARE REQUIRED AT THE
 STAIRS PER 905.2.2 FBC.
  
 8} THE RECEPTACLE IN THE GARAGE AT THE
 PANEL MUST BE GFI PER 210.8(A)(2).
  
 9} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PER 210.8(A)(6) AND SPACED
 PER210.52(C).
  
 10} A RECEPTACLE MUST BE ADDED AT THE
 PENINSULAR PER210.52(C)(3).
  
 11} PER 61G1-16.004 THE FIRMS BUSINESS
 LICENSE NUMBER(AA) MUST APPEAR IN THE
 TITLE BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  