| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE #6 EQUIPMENT GROUND FROM THE |
| METER TO THE PANEL MUST BE REMOVED PER |
| 250.6 AS IT ALLOWS A PARALLEL PATH TO |
| GROUND. |
| |
| 2} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALLED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BE RATED FOR THE AVAILABLE FAULT |
| CURRENT PER110.9. |
| |
| 3} PLEASE LIST THE REQUIRED ARC |
| FAULT PROTECTED CIRCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 4} IF THERE IS NO DISCONNECT AT THE |
| METER PLEASE SEE 230.70 CWPB |
| AMMENDMENTS FOR REQUIREMENT REGARDING |
| UNPROTECTED CONDUCTORS INSIDE THE |
| BUILDING. |
| |
| 5} A SERVICE RECEPTACLE MUST BE ADDED |
| FOR THE A/C PER 210.63. |
| |
| 6} PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING PER |
| 210.52(E). |
| |
| 7} SMOKE DETECTORS ARE REQUIRED AT THE |
| STAIRS PER 905.2.2 FBC. |
| |
| 8} THE RECEPTACLE IN THE GARAGE AT THE |
| PANEL MUST BE GFI PER 210.8(A)(2). |
| |
| 9} THE KITCHEN COUNTERTOP RECEPTACLES |
| MUST BE GFI PER 210.8(A)(6) AND SPACED |
| PER210.52(C). |
| |
| 10} A RECEPTACLE MUST BE ADDED AT THE |
| PENINSULAR PER210.52(C)(3). |
| |
| 11} PER 61G1-16.004 THE FIRMS BUSINESS |
| LICENSE NUMBER(AA) MUST APPEAR IN THE |
| TITLE BLOCK. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |