Plan Review Notes
Plan Review Notes For Permit 04080478
Permit Number 04080478
Review Stop B
Sequence Number 4
Notes
Date Text
2004-12-20 00:00:00RESPONSE TO FAX DATED 12/15/04
 ***NOT A PLAN REVIEW***
  
 AS DISCUSSED,
  
 1.)PERMIT CANNOT BE ISSUED WITHOUT
 IMPACT FEES.PLEASE SUBMIT BOTH STAMP
 AND RECEIPT.
  
 2.)THE PERMIT CAN BE ISSUED WITH A
 PROVISO THAT A SEPARATE PERMIT BE
 REQUIRED FOR THE SKYLIGHTS.
  
 3.)FAXED LETTER FROM THE ENGINEER WAS
 RECEIVED.IT STATES THAT THE ROOF IS
 ZONE 1, EFFECTIVE WIND AREA FROM 50 -
 100 SF.WHAT ABOUT ZONE 2&3?HOW WAS
 THE EFFECTIVE WIND AREA OF 50-100 SF
 FOR
 ZONE 1 DETERMINED?PROVIDE EFFECTIVE
 WIND AREA FOR ZONE 2 AND 3 WITH
 PRESSURES.
  
 4.)CORRECTION #4 REMOVED FROM THE
 LIST.
  
 5.)4X PLAN REVIEW FEE IS A MANDATORY
 FEE SET BY FLORIDA STATUTE AFTER THE
 THIRD TIME A COMMENT HAS NOT BEEN
 ADDRESSED.THIS FEE WOULD NOT APPLY TO
 COMMENTS 1&2.SHOULD COMMENTS 3 & 4
 NOT
 BE CLEAR, PLEASE CONTACT ME BEFORE
 RESUBMITTING.
  