Plan Review Notes For Permit 04080478 |
Permit Number |
04080478 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-12-20 00:00:00 | RESPONSE TO FAX DATED 12/15/04 | | ***NOT A PLAN REVIEW*** | | | | AS DISCUSSED, | | | | 1.)PERMIT CANNOT BE ISSUED WITHOUT | | IMPACT FEES.PLEASE SUBMIT BOTH STAMP | | AND RECEIPT. | | | | 2.)THE PERMIT CAN BE ISSUED WITH A | | PROVISO THAT A SEPARATE PERMIT BE | | REQUIRED FOR THE SKYLIGHTS. | | | | 3.)FAXED LETTER FROM THE ENGINEER WAS | | RECEIVED.IT STATES THAT THE ROOF IS | | ZONE 1, EFFECTIVE WIND AREA FROM 50 - | | 100 SF.WHAT ABOUT ZONE 2&3?HOW WAS | | THE EFFECTIVE WIND AREA OF 50-100 SF | | FOR | | ZONE 1 DETERMINED?PROVIDE EFFECTIVE | | WIND AREA FOR ZONE 2 AND 3 WITH | | PRESSURES. | | | | 4.)CORRECTION #4 REMOVED FROM THE | | LIST. | | | | 5.)4X PLAN REVIEW FEE IS A MANDATORY | | FEE SET BY FLORIDA STATUTE AFTER THE | | THIRD TIME A COMMENT HAS NOT BEEN | | ADDRESSED.THIS FEE WOULD NOT APPLY TO | | COMMENTS 1&2.SHOULD COMMENTS 3 & 4 | | NOT | | BE CLEAR, PLEASE CONTACT ME BEFORE | | RESUBMITTING. | | |
|