Plan Review Notes For Permit 04080478 |
Permit Number |
04080478 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-10-23 00:00:00 | ********* UNSAT ************* | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | FS 481.219 FOR MISSING REQUIRED INFOR- | | -MATION ON TITLE BLOCK FOR ARCH FIRM. | | THIS IS REQUIRED ON ALL SHEETS WHEATHER | | OR NOT COMMENT IS MADE BY OTHER REVIEW- | | -ER(S). | | THE AR# AND NAME WAS ADDED WHICH ONLY | | MEETS PART THE REQUIREMENT. | | PREVIOUS REVIEW NOTE **** | | | | 2)NOTE: PLEASE SEE LOAD CALCULATIONS | | HAVE BEEN CORRECTED, HOWEVER LOAD SHOWN | | IN LOAD CALCS SHOW LOAD @ 111A'S YET | | PANEL "A" INDICATES 105A'S? PLEASE | | CLARIFY THIS? PLEASE CORRELATE.(MISPRINT | | ? | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | ONLY INSERT NEW REVISED SHEETS INTO | | TWO COMPLETE SETS FOR REVIEW AND STAMP- | | -ING. | | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | AFFECT ON ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|