2004-08-23 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 IN TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004, FS 481.219.
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER REVIEWER
 'S.
  
 2)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MCB TO PANEL
 "B".
  
 3)NOTE: PLEASE CORRELATE LOAD INDICATED
 ON PANEL 'B' AND LOAD SHOWN ON PANEL"A".
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3.230.42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]