Plan Review Notes
Plan Review Notes For Permit 04080473
Permit Number 04080473
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-02 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SEE NEW ELECTRICAL SHEET
 IS BEING SUBMITTED W/OUT ORIG DETAILED
 PANEL SCHEDULE. PLEASE SEE NOTE #3 FROM
 PREVIOUS REVIEW. CIRCUITS FOR NEW ARE
 NOT ON PLAN.
 PLEASE SEE 700.12E ALSO FOR EM/EXT LTS.
 PLEASE SEE DIFFERENCES IN PREVIOUS
 PANEL
 SCHEDULE TO NEW NOW SHOWN.
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE PLANS NOW CONTAIN A
 COMPLETELY NEW "SIGNATURE" FOR THE
 ARCHITECT OF RECORD.
 PLANS ARE REQUIRED TO BE SIGNED WITH
 LEGAL
 "SIGNATURE". IF THIS IS ACTUAL LEAGL
 SIGNATURE, PLEASE PROVIDE A SIGNED,
 DATED AND SEALED NOTORIZED LETTER TO
 AFFIRM LEGAL SIGNATURE. THIS WILL BE
 PLACED IN A SIGNATURE FILE FOR FUTURE
 REFERENCE.PLANS MAY NOT BE SIGNED WITH
 MULTIPLE SIGNATURES.
 FS 481.025.
  
 PLEASE SEE POSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]