2004-11-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04080473
 ADD: 1500 N DIXIE# 308
 CONT: D. F. CONTRACTORS
 TEL: (561)502-1761
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2NDREVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)COMMENT# (2) FROM THE PREVIOUS REVIEW,
 1012.1.4. DURING ITS SWING, ANY DOOR IN
 A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST 1/2 OF THE REQUIRE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE
 THAN 7" INTO THE REQUIRED WIDTH.
 ALTHOUGH YOU DO NOT CONSIDER THIS THE
 EXIT, IT IS A CORRIDOR THAT STILL LEAD
 YOU TO AN EXIT. THE CORRIDOR WILL STILL
 REQUIRE 1/2 OF THE REQUIRED (36")
 MINIMUM WIDTH PLUS THE DOOR IN THE OPEN
 POSITION, WITH AN OUTSWING DOOR A
 MINIMUM WIDTH OF 54".
  
 2) SINCE THE TRAVEL DISTANCE FROM THE
 ENTRY TO THE BACK WALL OF THE BREAK ROOM
 IS OVER 75', 2 EXITS ARE REQUIRED,
 INDICATE EXIT LIGHTING ON THE PLAN.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026