Plan Review Notes
Plan Review Notes For Permit 04080473
Permit Number 04080473
Review Stop P
Sequence Number 1
Notes
Date Text
2004-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) MORE INFORMATION REQUIRED. INDICATE
 THE TYPE OF BUSINESS, AND EXPLAIN WHAT
 DRAWING ROOMS ARE.
 2) WATER COOLER SHALL BE ARI-1010 COM-
 PLIANT. SUBMIT MANUF. SPECIFICATIONS.
 SECTION 410.1
 3) SINK IN BREAKROOM SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 4) ACCESSIBLE TOILET ROOM SHALL COMPLY
 WITH 11-4.16, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. - W/C
 SHALL BE 18" FROM CENTER OF FIXTURE TO
 THE WALL, AND LAV SHALL BE MIN. 15" OFF
 WALL TO CENTER OF FIXTURE. SHOW THESE
 MEASUREMENTS ON THE DETAIL. SECTION
 104.2.1
 5) ORIGINAL SIGNATURE IS REQUIRED ON THE
 SEAL OF EACH SHEET. FAC 61G1-16.004(5)
 AND FS 481.2055 SIGNATURE STAMPS ARE NOT
 APPROVED.
 5) SHT 2 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS.
 A) BREAK ROOM SINK NOT SHOWN ON RISER.
 C) DRY HORIZONTAL VENTS ARE NOT APPROV-
 ED. SECTION 905.3
 D) LAVS IN ACCESSIBLE TOILET ROOM AND
 ADJACENT TOILET ROOM ARE NOT VENTED AND
 ARE "S" TRAPS WHICH ARE NOT APPROVE.
 SECTION 1002.3(5)
 E) W/C'S ON RISER DIAGRAM SHALL NOT BE
 TRAPPED AS THEY HAVE AN INTEGRAL TRAP IN
 THE FIXTURE AND THEY WILL BE DOUBLE TRA-
 PPED. SECTION 1002.1
 (SEE RED LINE CORRECTIONS ON RISER FOR
 EXAMPLES OF HOW TO CORRECT RISER.)
 6) SUBMIT A WATER RISER DIAGRAM. SECTION
 104.3.1.1
 7) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2
 8) INDICATE WHAT WILL BE PROCESSED IN
 THE PROCESSING ROOM. IF CHEMICALS/METALS
 ARE USED IN THE PROCESSING A DILUTION
 TANK OR SEPARATOR MAY BE REQUIRED.
 SECTION 104.2.1
 9) SECTION 903.1 EACH SANITARY DRAINAGE
 SYSTEM SHALL HAVE ONE MAIN VENT STACK
 THAT WILL EXTEND THROUGH TO THE OPEN AIR
  
 REVIEW BY KEN STEVENS