2004-08-19 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS ARE SEALED
 COPIES AND DO NOT CONTAIN ORIGINAL
 SIGNATURE AS REQUIRED UNDER FS 481.221
  
 2 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCS SHOWN ARE FOR A
 RESIDENTIAL HOUSE.
  
 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
 PLEASE ALSO INDICATE CIRCUITS FOR NEW
 ITEMS, TO CORRELATE WITH PANEL SCHEDULE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE SET OF ORIG TO BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]