Plan Review Notes For Permit 04080445 |
Permit Number |
04080445 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-13 00:00:00 | | | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE PROVIDE A CALCULATION | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | EXISTING LOADS AND THE EXISTING OR | | PROPOSED SERVICE SPECIFICATIONS PER | | 215.15. | | THE ELECTRICAL CONTRACTOR MUST SUBMIT | | SAME AT TIME OF APPLICATION. THE | | ELECTRICAL CONTRACTOR MUST SHOW THAT | | THE SERVICE IS ADEQUITE AND HAVE THE | | CALCULATIONS REVIEWED PRIOR TO CALLING | | INSPECTIONS, AND POST THE CALCULATIONS | | WITH THE PERMIT | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|