Plan Review Notes
Plan Review Notes For Permit 04080408
Permit Number 04080408
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-18 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE 210.12B OF 2002 NEC
 FOR ARC FAULT PROTECTION REQUIRED FOR
 BEDRMS.
 PLEASE ADJUST CIRCUITING.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND RISER. RISER MENTIONS, 1 1/2 CONDUIT
 AND PANEL SCHEDULE MENTIONS CABLE FOR
 FEEDERS??
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR NEW
 MCB BRKRS. 110.9/215.5
  
 4)NOTE: PLEASE SEE PLANS ARE MISSING
 REQUIRED TITLE BLOCK FOR ENGINEER.
 FAC 61G15-23.002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  