Plan Review Notes
Plan Review Notes For Permit 04080392
Permit Number 04080392
Review Stop E
Sequence Number 4
Notes
Date Text
2005-08-18 00:00:00** UNSAT **
  
 PLEASE SEE SOMEITEMS REDLINED ON
 PREVIOUS PLANS NEED TO BE REVISED.
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES PANEL TO BE INSTALLED AS A 42
 CIRCUIT PANEL, HOWEVER RISER DIAGRAM
 NOTES MENTIONS, A 30 CIRCUIT PANEL.
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE SOME REDLINED AREAS
 ON PLANS WHERE RECEPT SPACING DOES NOT
 SEEM TO MEET 210.52
 LIV RM, BEDRM'S #3 AND 4.
  
 3)NOTE: PLEASE SEE AREA WHERE AHU,
 ELECTRICAL PANEL AND WATER HEATER ARE
 LOCATED, MAY NOT BE A CLOSET.
 408.7,240.24 ETC.
 PLEASE SEE THIS RM/AREA IS TO BE LABLED
 AS MECH AND/OR ELEC RM.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]