Plan Review Notes For Permit 04080392 |
Permit Number |
04080392 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-08-18 00:00:00 | ** UNSAT ** | | | | PLEASE SEE SOMEITEMS REDLINED ON | | PREVIOUS PLANS NEED TO BE REVISED. | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE | | INDICATES PANEL TO BE INSTALLED AS A 42 | | CIRCUIT PANEL, HOWEVER RISER DIAGRAM | | NOTES MENTIONS, A 30 CIRCUIT PANEL. | | PLEASE CORRELATE. | | | | 2)NOTE: PLEASE SEE SOME REDLINED AREAS | | ON PLANS WHERE RECEPT SPACING DOES NOT | | SEEM TO MEET 210.52 | | LIV RM, BEDRM'S #3 AND 4. | | | | 3)NOTE: PLEASE SEE AREA WHERE AHU, | | ELECTRICAL PANEL AND WATER HEATER ARE | | LOCATED, MAY NOT BE A CLOSET. | | 408.7,240.24 ETC. | | PLEASE SEE THIS RM/AREA IS TO BE LABLED | | AS MECH AND/OR ELEC RM. | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|