2004-12-14 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| COMMENTS FROM THE PREVIOUS REVIEW, |
| ITEMS |
| #3 AND #4 WERE NOT ADDRESSED.PLANS |
| ARE |
| DATED 8/3 AND 8/6, SAME PLANS AS |
| REVIEWED PREVIOUSLY WITH NO REVISIONS. |
| |
| FOR YOUR CONVENIENCE, THE PREVIOUS |
| COMMENTS ARE AS FOLLOWS: |
| |
| 1.)PROVIDE DESIGN LOAD INFORMATION ON |
| THE PLAN AS WELL AS THE INFORMATION |
| REQUIRED BY FBC1609.1.72003 |
| AMENDMENTS. |
| |
| 2.)SHOW FBC TABLE 500 COMPLIANCE; |
| PROVIDE AREAS OF EXISTING BUILDING, |
| ADDITION AREA, DECLARE BUILDING TYPE, |
| SPRINKLED OR NONSPRINKLED AND |
| OCCUPANCY. |
| |
| 3.)SHOW HOW THE PANELS MEET FIRE |
| RESISTANCE REQUIREMENTS.CANOPIES IN |
| THE FIRE DISTRICT ARE TO CONFORM WITH |
| THE CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC, SECTION F102.2.8.ROOF |
| PANELS ARE NOT REQUIRED TO HAVE FIRE |
| RESISTANCE RATING UNLESS FIRE |
| RESISTANCE |
| RATING IS REQUIRED FBC1604.5(2).ROOF |
| FIRE RESISTANCE RATING IS REQUIRED CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC |
| F102.2.4. |
| |
| 4.)SHOW HOW QUALITY ASSURANCE WILL BE |
| ADDRESSED (LOCAL PRODUCT APPROVAL |
| APPLICATION), FAC9B-72. |
| |
| 5.)SEE ATTACHED FS553.80(2)(B). |
| |
| |