2004-08-31 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE PLANS SHOW A "FUTURE GARAGE". |
| PLEASE NOTE THAT COMPLIANCE WITH THE |
| BUILDING CODE OR CODES WHICH WILL BE IN |
| EFFECT AT THE TIME OF SUBMITTAL HAS NOT |
| PERFORMED FOR THIS FUTURE STRUCTURE |
| RELATIVE TO THIS AWNING. |
| |
| 2.)FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED FOR THE ROOF,FAC9B-72. |
| SEE WWW.FLORIDABUILDING.ORG.AN |
| APPLICATION WAS SUBMITTED BUT IS |
| INCOMPLETE.PLEASE NOTE THAT ITEM |
| #2, 7 THROUGH 10 ARE INCOMPLETE.PLEASE |
| SEE ATTACHED APPLICATION WITH CHECKLIST. |
| ORIGINAL DOCUMENTS REQUIRED, INCLUDING |
| SEALED TEST REPORT.A COPY OF A TEST |
| REPORT WHICH I FOUND ON THE INTERNET |
| IS INCLUDED FOR YOUR CONVENIENCE.IT |
| IS THE RESPONSIBILITY OF THE DESIGNER |
| TO DETERMINE WHETHER OR NOT THIS IS |
| THE PRODUCT YOU WISH TO INSTALL. |
| ALSO PLEASE SEE THE VALIDATION CHECKLIST |
| TO ASSIST YOU IN FILLING OUT THIS FORM. |
| ADDITIONAL INFORMATION IS ALSO |
| AVAILABLE IN THE RULE 9B-72 FOUND AT |
| WWW.FLORIDABUILDING.ORG. |
| |
| 3.)PROVIDE DESIGN LOAD INFORMATION |
| ON THE PLAN AS WELL AS THE INFORMATION |
| (WIND LOAD) REQUIRED BY FBC1609.1.7, |
| 2003 AMENDMENTS. |
| |
| 4.)YOU ARE CONNECTING TWO EXISTING |
| BUILDINGS TO BECOME ONE STRUCTURE. |
| PROVIDE AREAS OF THE EXISTING BUILDINGS, |
| DECLARE BUILDING TYPE AND OCCUPANCY, |
| SHOW COMPLIANCE WITH FBC TABLE 500. |
| |
| 5.)THE TEST REPORT WHICH I OBTAINED |
| FROM THE INTERNET (ENCLOSED) INDICATES A |
| FAILURE OF THE PANELS AT 161.2.THE |
| DECK CONNECTION ANALYSIS SHOW A DESIGN |
| PRESSURE OF -128.2 FOR ZONE 3.WHERE |
| IS THE SAFETY FACTOR FOR THE PANELS, |
| WHICH DO NOT APPEAR TO BE COMPLIANT |
| FOR ZONE 3 (ALTHOUGH THE CONNECTORS |
| ARE APPARENTLY COMPLIANT)?IS THIS |
| TEST FOR THE SAME PRODUCT? |
| |
| 6.)DELEGATED ENGINEERING IS TO BE |
| REVIEWED BY THE DESIGNER OF RECORD, |
| PLEASE REVIEW FAC61G15-30.005, .006. |
| DESIGN PERFORMED BY DELEGATED ENGINEER |
| IS TO BE IN CONFORMANCE WITH THE PLAN, |
| WHICH IS LACKING DESIGN CRITERIA. |
| |
| 7.)FOR THE CONNECTOR CALCS, A TITLE |
| BLOCK WITH ALL INFORMATION REQUIRED |
| BY FAC61G15-23.002 IS REQUIRED. |