Date Text
2004-08-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PLANS SHOW A "FUTURE GARAGE".
 PLEASE NOTE THAT COMPLIANCE WITH THE
 BUILDING CODE OR CODES WHICH WILL BE IN
 EFFECT AT THE TIME OF SUBMITTAL HAS NOT
 PERFORMED FOR THIS FUTURE STRUCTURE
 RELATIVE TO THIS AWNING.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE ROOF,FAC9B-72.
 SEE WWW.FLORIDABUILDING.ORG.AN
 APPLICATION WAS SUBMITTED BUT IS
 INCOMPLETE.PLEASE NOTE THAT ITEM
 #2, 7 THROUGH 10 ARE INCOMPLETE.PLEASE
 SEE ATTACHED APPLICATION WITH CHECKLIST.
 ORIGINAL DOCUMENTS REQUIRED, INCLUDING
 SEALED TEST REPORT.A COPY OF A TEST
 REPORT WHICH I FOUND ON THE INTERNET
 IS INCLUDED FOR YOUR CONVENIENCE.IT
 IS THE RESPONSIBILITY OF THE DESIGNER
 TO DETERMINE WHETHER OR NOT THIS IS
 THE PRODUCT YOU WISH TO INSTALL.
 ALSO PLEASE SEE THE VALIDATION CHECKLIST
 TO ASSIST YOU IN FILLING OUT THIS FORM.
 ADDITIONAL INFORMATION IS ALSO
 AVAILABLE IN THE RULE 9B-72 FOUND AT
 WWW.FLORIDABUILDING.ORG.
  
 3.)PROVIDE DESIGN LOAD INFORMATION
 ON THE PLAN AS WELL AS THE INFORMATION
 (WIND LOAD) REQUIRED BY FBC1609.1.7,
 2003 AMENDMENTS.
  
 4.)YOU ARE CONNECTING TWO EXISTING
 BUILDINGS TO BECOME ONE STRUCTURE.
 PROVIDE AREAS OF THE EXISTING BUILDINGS,
 DECLARE BUILDING TYPE AND OCCUPANCY,
 SHOW COMPLIANCE WITH FBC TABLE 500.
  
 5.)THE TEST REPORT WHICH I OBTAINED
 FROM THE INTERNET (ENCLOSED) INDICATES A
 FAILURE OF THE PANELS AT 161.2.THE
 DECK CONNECTION ANALYSIS SHOW A DESIGN
 PRESSURE OF -128.2 FOR ZONE 3.WHERE
 IS THE SAFETY FACTOR FOR THE PANELS,
 WHICH DO NOT APPEAR TO BE COMPLIANT
 FOR ZONE 3 (ALTHOUGH THE CONNECTORS
 ARE APPARENTLY COMPLIANT)?IS THIS
 TEST FOR THE SAME PRODUCT?
  
 6.)DELEGATED ENGINEERING IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD,
 PLEASE REVIEW FAC61G15-30.005, .006.
 DESIGN PERFORMED BY DELEGATED ENGINEER
 IS TO BE IN CONFORMANCE WITH THE PLAN,
 WHICH IS LACKING DESIGN CRITERIA.
  
 7.)FOR THE CONNECTOR CALCS, A TITLE
 BLOCK WITH ALL INFORMATION REQUIRED
 BY FAC61G15-23.002 IS REQUIRED.