Plan Review Notes For Permit 04080381 |
Permit Number |
04080381 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-03-03 00:00:00 | DENIED | | | | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR | | THE COUNTY IMPACT FEES. | | | | 2) SUBMIT TWO COPIES OF ENERGY | | CALCULATIONS FOR THE STRUCTURE AS | | REQUIRED BY CHAPTER 13 OF THE FLORIDA | | BUILDING CODE. NOTE: THE OWNER/AGENT IS | | REQUIRED TO SIGN AND DATE THE FORM. | | | | 3) SUBMIT UL OR OTHER LISTING | | INFORMATION FOR THE PRE-FAB FIREPLACE | | AND CHIMNEY. THE INFORMATION THAT WAS | | SUBMITTED DOES NOT PROVIDE ANY | | INFORMATION RELATED TO BEING LISTED BY | | ANY APPROVED ENTITY. | | | | 4) SHOP DRAWINGS FOR EXTERIOR GUARD | | RAILS WILL BE REQUIRED PRIOR TO | | INSTALLING. | | | | 5) THE NOTICE OF COMMENCEMENT WAS | | RECORDED MORE THAN 90 DAYS PRIOR TO | | START OF WORK. THEREFORE, IT IS NULL AND | | VOID AND WILL NEED TO BE RE-RECORDED | | BEFORE PERMIT IS ISSUED. SEE FS 713.13. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|