Plan Review Notes
Plan Review Notes For Permit 04080381
Permit Number 04080381
Review Stop B
Sequence Number 3
Notes
Date Text
2005-03-03 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) SUBMIT TWO COPIES OF ENERGY
 CALCULATIONS FOR THE STRUCTURE AS
 REQUIRED BY CHAPTER 13 OF THE FLORIDA
 BUILDING CODE. NOTE: THE OWNER/AGENT IS
 REQUIRED TO SIGN AND DATE THE FORM.
  
 3) SUBMIT UL OR OTHER LISTING
 INFORMATION FOR THE PRE-FAB FIREPLACE
 AND CHIMNEY. THE INFORMATION THAT WAS
 SUBMITTED DOES NOT PROVIDE ANY
 INFORMATION RELATED TO BEING LISTED BY
 ANY APPROVED ENTITY.
  
 4) SHOP DRAWINGS FOR EXTERIOR GUARD
 RAILS WILL BE REQUIRED PRIOR TO
 INSTALLING.
  
 5) THE NOTICE OF COMMENCEMENT WAS
 RECORDED MORE THAN 90 DAYS PRIOR TO
 START OF WORK. THEREFORE, IT IS NULL AND
 VOID AND WILL NEED TO BE RE-RECORDED
 BEFORE PERMIT IS ISSUED. SEE FS 713.13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  