2004-08-16 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALLED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BE RATED FOR THE AVAILABLE FAULT |
| CURRENT PER 110.9. |
| |
| 2} THE ELECTRODE MUST BE CONNECTED TO |
| FOOTER STEEL PER 250.52(A)(3). |
| |
| 3} THE SMOKE DETECTORS MUST BE ON AN |
| ARC FAULT CIRCUIT PER 210.12, THE NOTES |
| REGARDING THE KITCHEN OR BATHROOM |
| CIRCUIT WOULD INDICATE THEY WOULD NOT |
| BE ARC FAULT PROTECTED. PLEASE CLARIFY. |
| |
| 4} PLEASE PROVIDE A PANEL SCHEDULE SO |
| BRANCH CIRCUIT COMPLIANCE CAN BE |
| DETERMINED.210.12, 210.11(C) ALL,ETC. |
| |
| 5} IT IS UNCLEAR WHETHER THE MAIN PANEL |
| IS LOCATED NEXT TO THE METER OR |
| ELSEWHERE. PLEASE CLARIFY AND BE AWARE |
| OF ARTICLE 230.70 WPB AMMENDMENTS |
| REGARDING SERVICE DISCONNECTING MEANS. |
| |
| 6} PLEASE SEE THAT RECEPTACLE SPACING |
| DOES NOT COMPLY WITH 210.52(A)(1) & (2) |
| IN THE LIVING ROOM, MASTER BEDROOM AND |
| BEDROOM #2, SEE REVIEWED SET OF PLANS. |
| |
| 7} THE MASTER BATH NEEDS A RECEPTACLE |
| (GFI) TO COMPLY WITH 210.52(D). |
| |
| 8} PLEASE SEE MISSING RECEPTACLE IN THE |
| FRONT PER 210.52(E). |
| |
| 9} THE ISLAND RECEPTACLE (KITCHEN) MUST |
| BE GFI PER 210.8(A)(6). |
| |
| 10} THE BATH OFF THE DINING ROOM MUST |
| HAVE A GFI PER 210.52(D). |
| |
| 11} PLEASE LIST THE REQUIRED ARC |
| FAULT PROTECTED CIRCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |