 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} THE ELECTRODE MUST BE CONNECTED TO
 FOOTER STEEL PER 250.52(A)(3).
  
 3} THE SMOKE DETECTORS MUST BE ON AN
 ARC FAULT CIRCUIT PER 210.12, THE NOTES
 REGARDING THE KITCHEN OR BATHROOM
 CIRCUIT WOULD INDICATE THEY WOULD NOT
 BE ARC FAULT PROTECTED. PLEASE CLARIFY.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE SO
 BRANCH CIRCUIT COMPLIANCE CAN BE
 DETERMINED.210.12, 210.11(C) ALL,ETC.
  
 5} IT IS UNCLEAR WHETHER THE MAIN PANEL
 IS LOCATED NEXT TO THE METER OR
 ELSEWHERE. PLEASE CLARIFY AND BE AWARE
 OF ARTICLE 230.70 WPB AMMENDMENTS
 REGARDING SERVICE DISCONNECTING MEANS.
  
 6} PLEASE SEE THAT RECEPTACLE SPACING
 DOES NOT COMPLY WITH 210.52(A)(1) & (2)
 IN THE LIVING ROOM, MASTER BEDROOM AND
 BEDROOM #2, SEE REVIEWED SET OF PLANS.
  
 7} THE MASTER BATH NEEDS A RECEPTACLE
 (GFI) TO COMPLY WITH 210.52(D).
  
 8} PLEASE SEE MISSING RECEPTACLE IN THE
 FRONT PER 210.52(E).
  
 9} THE ISLAND RECEPTACLE (KITCHEN) MUST
 BE GFI PER 210.8(A)(6).
  
 10} THE BATH OFF THE DINING ROOM MUST
 HAVE A GFI PER 210.52(D).
  
 11} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  